Corrosion Defence: Underground Gas Storage

Published on by in Technology

Corrosion Defence: Underground Gas Storage

NIST Corrosion Lab Tests Suggest Need for Underground Gas Tank Retrofits

A hidden hazard lurks beneath many of the roughly 156,000 gas stations across the United States.

The hazard is corrosion in parts of underground gas storage tanks—corrosion that could result in failures, leaks and contamination of groundwater, a source of drinking water. In recent years, field inspectors in nine states have reported many rapidly corroding gas storage tank components such as sump pumps. These incidents are generally associated with use of gasoline-ethanol blends and the presence of bacteria, Acetobacter aceti, which convert ethanol to acetic acid, a component of vinegar.

Following up on the inspectors' findings, a National Institute of Standards and Technology (NIST) laboratory study* has demonstrated severe corrosion—rapidly eating through 1 millimeter of wall thickness per year—on steel alloy samples exposed to ethanol and acetic acid vapors. Based on this finding, NIST researchers suggest gas stations may need to replace submersible pump casings, typically made of steel or cast iron, sooner than expected. Such retrofits could cost an estimated $1,500 to $2,500 each, and there are more than 500,000 underground gas storage tanks around the country.

The NIST study focused only on sump pump components, located directly below access covers at filling stations, just above and connected to underground gas storage tanks. The sump pumps move fuel from underground tanks to the fuel dispensers that pump gas into cars. These underground tanks and pipes also may be made of steel and could be vulnerable, too. "We know there are corrosion issues associated with the inside of some tanks. We're not sure, at this point, if that type of corrosion is caused by the bacteria," NIST co-author Jeffrey Sowards says.

Much of the U.S. fuel infrastructure was designed for unblended gasoline. Ethanol, an alcohol that can be made from corn, is now widely used as a gasoline additive due to its oxygen content and octane rating, or antiknock index. A previous NIST study found that ethanol-loving bacteria accelerated pipeline cracking.**

For the latest study, NIST researchers developed new test methods and equipment to study copper and steel alloy samples either immersed in ethanol-water solutions inoculated with bacteria, or exposed to the vapors above the medium—conditions mimicking those around sump pumps. Corrosion rates were measured over about 30 days.

The NIST study confirmed damage similar to that seen on sump pumps by field inspectors. The worst damage, with flaky iron oxide products covering corrosion, was found on steel exposed to the vapors. Copper in both the liquid and vapor environments also sustained damage, but corrosion rates were slower. Steel corroded very slowly while immersed in the liquid mixture; the NIST paper suggests bacteria may have created a biofilm that was protective in this case.

Source: NIST