Sodium Hypochlorite Tank vent

Published on by in Technology

We have big electro-chlorination plant and three large storage tanks.

I need to get recommendation on the type of “tank vent” which can prevent too much mist come out of the tank due to aeration of the tank by blowers.

Taxonomy

5 Answers

  1. Are using air to sparge or stir the liquid in the tank to keep it from settling? Or, are the blowers just for sweeping the head space of the tank to remove vapors? If its just the head space, you could start by installing a demister box with impinge plates to cause mist droplets to condense and drop out. Conventional wet scrubbers for air pollution control use chevron blade demisters after the packed bed, a chevron type demister would probably work in this case as long as the air velocity isn't too high.

     

    1 Comment

  2. What are the blowers doing with you storage tanks? Install a water locker of ea. tank and bring the exhaust's ea. or communicatet over roof, in case it's in the building. Anyhow  far from people breathing height.